I have 2 well pumps that serve the same pressure zone. The pumps are rotated lead/lag on even/odd days. One pump runs on even numbered days and the other on odd days.
How can I setup a control scheme to do this? I don't see anything in the controls to be able to accomplish this other than time from start but then I would have to setup multiple controls to turn pumps on/off after 24/48/72/96 hrs.
Watercad V8i SS6 (08.11.06.58)
Thanks
This article in our Wiki offers another option, involving the use of pipe status as a variable:
Controls for alternating or cycling between multiple pumps
I've incorporated Sushma's time-based suggestion as another option.
Regards,
Jesse DringoliTechnical Support Manager, OpenFlowsBentley Communities Site AdministratorBentley Systems, Inc.