How can I model an RPZ device (reduced pressure principle backflow preventer)?


Product(s):HAMMER
Version(s):08.11.XX.XX and 10.00.XX.XX
Area:Modeling

Problem

How can I model an RPZ device (reduced pressure principle backflow preventer)?

Solution

Currently, HAMMER cannot directly model this device. One of two possible workarounds can be employed:

1) Place two check valve nodes and model a TCV valve between them that discharges to a reservoir. Develop a pattern of valve closure based on when the reverse flow occurs.

2) Use a surge valve between the two check valve nodes, modeled as a SAV.

[Solution ID#: 500000067195]