RE: I couldn't generate floor load in one panel.i have done the intersect. but could not generate the floor load. It is a RCC framed structure using staadpro v8i series 6 suggestions are appreciated. Thanks in advance
Modestas
There are some duplicate nodes in your model. You can find it by doing a duplicate node check with a tolerance of 0.01 m. If you get rid of these duplicate nodes, the floor loads should be generated fine.