<?xml-stylesheet type="text/xsl" href="https://communities.bentley.com/cfs-file/__key/system/syndication/rss.xsl" media="screen"?><rss version="2.0" xmlns:dc="http://purl.org/dc/elements/1.1/"><channel><title>Paul Trenter's Activities</title><link>https://communities.bentley.com/members/84650d6d_2d00_769f_2d00_4c63_2d00_8a60_2d00_3682415729b5</link><description>Paul Trenter's recent activity</description><dc:language>en-US</dc:language><generator>Telligent Community 12</generator><item><title>Fail Type 7</title><link>https://communities.bentley.com/products/building/performance/f/hevacomp-forum/223796/fail-type-7</link><pubDate>Wed, 22 Dec 2021 10:30:28 GMT</pubDate><guid isPermaLink="false">6dad98f5-dbc9-4c4d-a9ba-e9da8dc6aa8e:26d79b0f-8d86-4c3f-b418-f46059df27b1</guid><dc:creator>Paul Trenter</dc:creator><description>&lt;h1 class="name"&gt;Connect Fail Type 7&lt;/h1&gt;
&lt;div class="author header thread-starter"&gt;I noticed a question back in 2019 with regard to fail type 7 as below.&lt;br /&gt;&lt;span class="post-date"&gt; &lt;/span&gt;&lt;/div&gt;
&lt;div class="author header thread-starter"&gt;&lt;/div&gt;
&lt;div class="content"&gt;
&lt;p&gt;&lt;span style="color:#33cccc;"&gt;Under the fail help, fail type 7 is determined as &amp;quot;Fails as no I2t data is available for the devices, assume a failure by default&amp;quot;.&lt;/span&gt;&lt;/p&gt;
&lt;p&gt;&lt;span style="color:#33cccc;"&gt;I assume that the I2t data for the specific devices is not present in the data file for that particular device, in this instance Schneider Mirologic ACB&amp;#39;s.&lt;/span&gt;&lt;/p&gt;
&lt;p&gt;&lt;span style="color:#33cccc;"&gt;With no I2t data the calculation defaults to unlimited energy let through, which then fails the k2s2 &amp;gt; I2t test.&lt;/span&gt;&lt;/p&gt;
&lt;p&gt;&lt;span style="color:#33cccc;"&gt;As such I&amp;#39;m left with a failure on the main supply where I&amp;#39;m using Schenider ACB&amp;#39;s on both the LV supply (in this case an outgoing transformer) and on the incoming side of the main panel board.&lt;/span&gt;&lt;/p&gt;
&lt;p&gt;&lt;span style="color:#33cccc;"&gt;Using the generic ACB on the LV feeder overcomes the issues, but then gives me a discrimination problem with the down stream Schneider ACB.&amp;nbsp; &amp;nbsp;&amp;nbsp;&lt;/span&gt;&lt;/p&gt;
&lt;p&gt;&lt;span style="color:#33cccc;"&gt;Why is the I2t data not included in the calculation? And how do I overcome the issues?&lt;/span&gt;&lt;/p&gt;
&lt;p&gt;&lt;span style="color:#000000;"&gt;Schneider ACB&amp;#39;s must be one of the most commonly used protective devices of this type.&amp;nbsp; &lt;/span&gt;&lt;/p&gt;
&lt;p&gt;&lt;span style="color:#000000;"&gt;I too have the need to produce calculations for scrutiny by a Consultant.&lt;/span&gt;&lt;/p&gt;
&lt;p&gt;&lt;span style="color:#000000;"&gt;When will this issue be resolved?&amp;nbsp; Using a Generic ACB does not satisfy the Consultant, they require the verified calculations using the devices we will be installing.&lt;/span&gt;&lt;/p&gt;
&lt;p&gt;&lt;span style="color:#000000;"&gt;Please advise when a fix will be provided.&lt;/span&gt;&lt;/p&gt;
&lt;/div&gt;&lt;div style="clear:both;"&gt;&lt;/div&gt;</description></item><item><title>Ask A Question I</title><link>https://communities.bentley.com/achievements/460ac7df-7ccc-4c42-a204-9e05eef3be09</link><pubDate>Wed, 22 Dec 2021 05:26:57 GMT</pubDate><guid isPermaLink="false">6dad98f5-dbc9-4c4d-a9ba-e9da8dc6aa8e:96c37bda-f30d-4959-b6b5-f1bccbd56cd3</guid><dc:creator /><description>Ask a question in a forum.</description></item></channel></rss>