An iterative process is used to carry out pipe sizing in Netsys. What follows is an explanation of the methods used.
Initially pipe sizes are estimated by calculating flow rates at emitters based on the following formula:
This gives an initial flow rate based on the flow and return temperatures at the boiler. The program then works these flow rates back through the system to give a total flow rate at the boiler. Pipe sizes are estimated based on these initial flow rates.
Pipe work emissions are then calculated and used to re-compute the flow rates through the system and are worked back to give a new total flow rate at the boiler. This flow rate is then proportioned through the system by connected load. Below is a simple example:
Pipes are then resized on the new flow rates and heat emissions recomputed again. This process continues until no pipes change size.
Customers often look at parts of their system in isolation and use the equation at the top of the page to check flow rates to an emitter using the flow and return temperatures at the boiler (set in System Defaults). However the flow and return temperatures at the emitters will not be the same as at the boiler due to mains losses and so this calculation is inaccurate. The example below shows how the use of the boiler flow and return temperatures differs from what the true flow and return temperature may be.
Using the flow rate equation at the beginning of this document the customer would get the following flow rate for the pipe feeding Emitter 3.
However due to losses from the mains the flow and return temperatures at the emitter will not be 86oC and 76oC but may be more like 85oC and 80oC. The equation will then change thus:
This shows that the flow rate at the emitter could be more than double the value calculated using the boiler flow and return temperatures.
Product TechNotes and FAQs
Building Product TechNotes And FAQs
How do I convert my Version 18 Connect projects to Version 24
How to move custom reports to a new version
How to reinstall Crystal Reports
Glazing Data - How Do I Calculate Solar Gain Factors
Creating a template project
CAD Model Design - Elevating roofs using Roof Points
CAD Model Design - How to specify an Angle to South
Defining lighting control and daylight factors for Design Simulation calculations
Calculations - Using Fresh air loads in Design Database
DXF Import issues - 3D floors misaligned
Why does Design Database tell me my project is a CAD project
How to add a company logo to your reports
Hardware Specification - What do I need to run Bentley Hevacomp?
How do I automatically roll out over a network
Why does my installation generate a 1608 or 1628 error
How do I modify my firewall settings in XP to allow the software to run
How do I set up my licence server on a Novell network
What port does the Licence Manager use
Why does the Licence Manager fail to restart on a server reboot
Heating and Chilled water - Higher than expected flow rates
How do I add floor change connectors in Netsys
Converting Flow Rates from Loading Units To Litres Per Second
How do I fix or unfix a vertical pipeduct section
Why does NETSYS tell me my project is a CAD project
Adding wall mounted luminaires
Why Do Lumen Reports Show NA
How do I create a Summer Design Day based on the CIBSE Summer Design Year data
What is dynamic simulation
Bentley homepage
HevacompMechanical Designer
Bentley Technical Support KnowledgeBase
Bentley LEARN Server
Bentley's Technical Support Group requests that you please confine any comments you have on this Wiki entry to this "Comments or Corrections?" section. THANK YOU!