Reporting pressure available at the exact total needed fire flow

  Applies To 
  Product(s): WaterGEMS, WaterCAD
  Version(s): CONNECT Edition, V8i
  Original Author: Mark Pachlhofer, Bentley Technical Support Group

Problem

If I want to see how much pressure is available exactly at the total needed fire flow, do I need to set the upper limit equal to the needed fire flow?

Solution

There are separate result fields that shows the residential and zone pressure at exactly the needed fire flow. Click the Edit button at the top of the Fire Flow Node Table and add the fields "Pressure (Calculated Residual @ Total Flow Needed)" and "Pressure (Calculated Zone Lower Limit @ Total Flow Needed)".

You can also consider a hydrant flow curve.

See Also

How does the Automated Fire Flow analysis work?

Understanding Automated Fire Flow Results

WaterGEMS and WaterCAD Automated Fire Flow FAQ  