Can SWMM Control Sets be used in Bentley's storm and sewer products? How is the data inputted and utilized?
SWMM Control Sets allow a SewerGEMS or CivilStorm user to control the behavior of elements based on the condition in some other element using control rules set based on the SWMM program. These control rules are based on the syntax rules presented below and are used only by the Explicit (SWMM) solver. SWMM Control Sets can be used to turn pumps on and off. They can also be used to adjust the weir height and orifice opening for conduit control structures. Additional information on these can be found in the SewerGEMS and CivilStorm Help documentation.
The following screenshot shows the objects that can be used in SWMM Control Sets:
The meaning of SETTING depends on the object being controlled:
Node (depth, head, inflow), link (flow, depth), pump flow, and simulation time are typically used in the condition part of the Control Set. The pump status and orifice and weir settings are used in the action statement. The formatting of this statement is similar to the logical control statement that users of WaterGEMS, WaterCAD, and SewerCAD may be familiar with: IF condition THEN action ELSE action2. Priorities can also be added that will make it so a given control takes precedence over another control.
As SWMM Control Sets are used with pumps or control structures on conduits, these elements will need to be present in the model. Go to Components > SWMM Extensions > Control Sets to open the SWMM Control Sets dialog. This is where you can create and edit your control sets. To create a new control set, click the New button in the upper left.
The Control Editor Pane on the right side of the dialog allows you to define SWMM controls. Each control rule is a series of statements of the form:
RULE ruleID IF condition_1 AND condition_2 OR condition_3 AND condition_4 Etc. THEN action_1 AND action_2 Etc. ELSE action_3 AND action_4 Etc. PRIORITY value
where keywords are shown in all caps, ruleID is an ID label assigned to the rule, condition_n is a Condition Clause, action_n is an Action Clause, and value is a priority value (e.g., a number from 1 to 5).
NOTE: Only the RULE, IF and THEN portions of a rule are required; the other portions are optional. Blank lines between clauses are permitted and any text to the right of a semicolon is considered a comment. Expected Units for control sets are as follows: Flow: cfs; Length: feet; Time: hours. No units are actually entered in the control set. ELSE statements may need to be placed on a separate line.
For example, suppose you wanted to create a control where a weir fraction open changes based on the flow on a given conduit. A zero could be used for closed and a 1.0 for open, plus values in between. The control would be formatted like this:
RULE 1AIF LINK CO-1 FLOW > 10THEN WEIR W1 SETTING = 0.5
In this case, you would enter "LINK" before the conduit label so that the control knows what type of element it is. In the action statement (THEN), you include the element type as well as a label. In the example above the label is "W1". This is the label of the weir as seen in the Conduit Control Structures dialog:
Note: older versions had a "SWMM Label" field where the label would be entered.
The next step for using SWMM Control Sets is to open the calculation option properties. Set the property field Apply SWMM Control Set to "True." For the property SWMM Control Set, click the pulldown menu and select the name.
Keep in mind that your SWMM Control Set will typically have more than one entry. For instance, you will have controls for the pump turning on and off. For conduit control structures, you would have different weir or orifice settings for different simulation times or flow values.
The following are examples of control rules that can be used in SWMM Control Sets:
Simple time-based pump control
RULE R1 IF SIMULATION TIME > 8 THEN PUMP 12 STATUS = ON ELSE PUMP 12 STATUS = OFF ;
Multi-condition orifice gate control
RULE R2A IF NODE 23 DEPTH > 12 AND LINK 165 FLOW > 100 THEN ORIFICE R55 SETTING = 0.5
RULE R2B IF NODE 23 DEPTH > 12 AND LINK 165 FLOW > 200 THEN ORIFICE R55 SETTING = 1.0
RULE R2C IF NODE 23 DEPTH <= 12 OR LINK 165 FLOW <= 100 THEN ORIFICE R55 SETTING = 0 ;
Pump station operation (as in a SWMM4 Type5 pump)
RULE R3A IF NODE N1 DEPTH > 5 THEN PUMP N1A STATUS = ON
RULE R3B IF NODE N1 DEPTH > 7 THEN PUMP N1B STATUS = ON
RULE R3C IF NODE N1 DEPTH <= 3 THEN PUMP N1A STATUS = OFF AND PUMP N1B STATUS = OFF
Modeling gate valve opening and closing based on pressure transducer reading
Conduit start/stop control structures
Creating Controls - Conditions, Actions, and Control Sets