You are currently reviewing an older revision of this page.
Dashboard for At-a-glance indication if “patterned” variables for the zone lie within the expected range of values. Particularly useful to quickly spot any anomalies (that can represent bursts, leaks, tank overflows, pressure problems, maintenance works, etc) in real time, inside a specific zone.
Zones should correspond to isolated areas of the system, surrounded by closed valves and where all inflows and outflows (if exist) must be measured. Zones can include for example DMA (District Metered Areas), pressure zones or operational zones. The configuration of the inflow and outflow sensors as well as tanks levels that may exist inside the zone are configured in the Zones configuration page (at the administration level) by the user. As an important note, the tank levels that should be considered for the zones balance are only those that are inside the zones boundary, this means that if a zone is supplied by a tank and the inflow sensor is immediately downstream the tank, this tank level must not be considered.
By default a 3x3 grid of flow sensors is displayed charting readings of the past 24 hours and a forecast of 6 hours. The number of zones to be displayed simultaneously is limited by page - the user has the option to navigate to the following pages to see the remaining zones or search for a specific one.
The grey band on each chart represents a pattern computed from one month of historical sensor readings within the zone. A pattern corresponds to an expected behavior for the zone. In OpenFlows WaterSight patterns are computed for each zone using advanced data analytics (statistic equations together with machine learning techniques to remove outliers or bad data). Real (re-sampled) values are represented as a black, red or orange circles. Whenever real data (re-sampled) goes outside the pattern confidence bands (above percentile 95 or below percentile 5 of the pattern), an outlier is identified and the value is color coded with a red circle.
Note: Zones will display in descending priority, highest priority first. Zones with a priority of 0 will not be displayed in the overview. The priority of each zone is defined at the Zones Configuration, in the administration page.
Filters the grid of zones to the ones containing the word fragment typed in (case-insensitive).
Allows to switch between Small, Medium and Large tiles.
Note: a double-click inside the sensor chart area will navigate to the Zone Details of that specific zone.